Hello, if you already have an account, log in.
You are a new user?
Create an account
Temperature controller Hynux AX9
292.68zł Tax excluded




Hynux AX9 PID temperature controller
Compact, precise controller for demanding users. The characteristic feature is high measurement accuracy. An additional advantage is the ability to operate both an SSR relay and a normal contactor.

Technical data
Name | Description |
Power supply | 185-230V AC |
Adjustable temperature range | up to 2000°C |
Control output |
|
Resolution of indications and settings | 0,1°C |
Control | PID, ON/OFF |
Display | Setpoint temperature display, current temperature display |
Programmable alarms | 2 programmable relay alarms (3A) |
Possibility to connect sensors | (RTD) resistive: PT100 (TC) thermocouples: J,K,E,S,T,B |
Front panel dimensions | 96x96mm |
Wiring diagram

Dimension

What is PID? Application.
PID is an internal algorithm stored in the memory of the control device.It can be regarded as an additional function that improves control and steering because it adapts to the system in which it is installed. Without automatic controllers, all tasks of regulation, man would have to be done manually! |
PID regulation

PID control is used for precise temperature control without the task of hysteresis (deviation). The control here is done by pulse actuation of the control output, in this case it is worth using solid-state relays (SSR), which are not sensitive to frequent switching.
For more information, see our blog: What is PID? |
Auto-tuning function

The controller has an auto-tuning function, which is activated only once after the controller is installed in the machine or furnace. It consists in the fact that the controller selects the PID values by itself in order to maintain the set temperature as optimally and accurately as possible. The PID parameters can also be changed manually. The controller can maintain the temperature on the extruder with an accuracy of 0.1°C.
For more information, see our blog: Selecting PID settings in practice. |
Alarms
AX series controllers support two independent alarms AL1/AL2 which can be assigned to relay outputs RLY1/RLY2.If an alarm is not assigned to a relay output, no settings will be possible for that alarm.
High alarm
Example
The controller will sound an alarm when the temperature rises to 27°C
Low alarm
Example
The controller will sound an alarm when the temperature drops below 24°C
Alarm out of range
Example
The controller will sound an alarm when the temperature falls below 24°C or rises to 26°C
Out of range alarm
Example
The controller will sound an alarm when the temperature rises above 20°C or falls below 30°C
Alarm holding function ( Standby)
When the standby function is used, the alarm output (ON) set in LOW mode is prevented from being driven from the time the controller is turned on until the set temperature is reached.
Locking the alarm in the LOCK function
When output LOCK is selected for an Alarm, the Alarm is not cleared even if the limiting conditions of that Alarm are no longer present. To delete an alarm with the LOCK option, hold down the "up arrow" key for 2s. Example: If you set a temperature of 100 C for AL1 and set the option "alarm 1 output LOCK - ON", then when this value is exceeded, AL1 will be triggered which will be sustained despite the temperature drop to, for example, 75 °C.
LBA (Loop break Alarm)
When 0% or 100% of the setpoint is reached in PID mode, timing starts. In addition, thanks to this function, it is possible to detect the failure of a heater or sensor after by monitoring the rate of change of the measured value during the period set in the Loop Break Alarm Time parameter. In addition, it is possible to set the Loop break alarm dead zone (LBA).
If 100% of the setpoint value in PID mode is reached, and the temperature rises above the value declared in the "Loop Break Alarm Temperature" parameter within the time specified by the "Loop Break Alarm Time " parameter, the LBA alarm will be activated. If 0% of the setpoint value in PID mode is reached, and the temperature drops below the value declared in the "Loop Break Alarm Temperature" parameter within the time specified by the "Loop Break Alarm Time " parameter, the LBA alarm will be activated.
Phase Control
The control cycle is coupled to the frequency of the supply voltage. RANDOM ON/OFF SSR relays are recommended for this mode of operation (recommended for inductive loads, where delays resulting from the use of ZERO-CROSSING relays may cause malfunctions).
Timeshare Cycle Control (Default Mode).
The controller controls the relay by cyclically adjusting the driving time during a control cycle specified by the user via the Ct parameter. The most common mode of operation for typically resistive loads ( heating elements or others with low impedance ).



- Adjustment
- PID, ON/OFF
- Hysteria
- 0,1~10°C
- Control output
- Relay, Voltage, Current
- Maximum load of the control output
- 3A
- Measurement range
- 0~1999°C
- Mode of operation
- Heating or Cooling
- Display resolution
- 0,1°C
- Alarm output
- RLY 1 relay (3A), RLY 2 relay (3A)
- Obsługa czujników
- (RTD) Resistive PT100, KPT100 / (TC) Thermocouple J,K,E,S,T,B,N,U,W,PLII
- Panel
- 96x96mm
- Assembly
- In a board or hermetic, wall-mounted enclosure
- Power supply
- 185-230V AC
In Stock
In Stock
In Stock
In Stock
In Stock
101.63zł Tax excluded
There are not enough products in stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
In Stock
Precision measurement in industry
10 years of experience
in the industry
14-day right of return
of ordered goods
secure and convenient
online payments
consultant assistance during
ordering
Add a review
Add a review