For example, the MG14 liquid level meter and PS-02-420 sensor in a tank with a height of 180 cm. Enter the alarm menu and hold the key for 3 seconds. Then enter the password to change the calibration settings
Set the input signal type (4 mA-20 mA)
Set the values for the minimum sensor signal (4 mA = 0 cm)
Set the values for the maximum sensor signal (20 mA = 200 cm)
Set the values for 0% minimum tank (0% = 0cm)
Set the values for 100% max tank (100% = 180cm)
Set the value for the low alarm (low alarm will activate below the value of 20 cm)
Set the hysteresis value for the low alarm (low alarm will turn off when the level rises by 20 cm to the AL value)
Set the value for the high alarm (high alarm will activate above the value of 180cm)
Set the high alarm hysteresis values (the high alarm will turn off when the level drops 10 cm from the AH value)
The AL (low alarm) relay will turn on below the 20cm value (), and turn off above the 40cm value ( + ).
The AH (high alarm) relay will turn on above the 180cm value (), and turn off below the 170cm value ( - )
You can find the set at the link below:
https://termipol.pl/zestaw-pomiar-poziomu-wody-0-2m-mg14-ps-02-420.html
Gotowy zestaw pomiarowy umożliwiający pomiar i nadzór poziomu wody w studni lub dowolnym zbiorniku. Dzięki połączeniu urządzeń wyświetlających wynik pomiaru oraz czujnika możliwa jest ciągła kontrola poziomu przy użyciu jednego czujnika. Wbudowane cztery przekaźnikowe wyjścia alarmowe ALL (b. niski), AL (niski), AH (wysoki), AHH (b. wysoki) pozwalają uruchamiać urządzenia wykonawcze takie jak: pompa, elektrozawór itp. Przewód czujnika można przedłużyć we własnym zakresie do 50m. Umożliwia to zastosowanie poniższego zestawu np. przydomowym zbiorniku na wodę deszczową.